OpenStudio Results

Model Summary


Information Value Units
Building Name NECB 2011-HighriseApartment-NECB HDD Method-CAN_PQ_Kuujuaq.719060_CWEC.epw created: 2017-06-30 13:15:45 +0000 building_name
Net Site Energy 4,653,479 kBtu
Total Building Area 84,351 ft^2
EUI (Based on Net Site Energy and Total Building Area) 55.17 kBtu/ft^2
OpenStudio Standards Building Type HighriseApartment

Value
Weather File Kuujuaq PQ CAN WYEC2-B-15605 WMO#=719060
Latitude 58.10
Longitude -68.4
Elevation 121 (ft)
Time Zone -5.0
North Axis Angle 0.00
ASHRAE Climate Zone

Maximum Dry Bulb (F) Daily Temperature Range (R) Humidity Value Humidity Type Wind Speed (mph) Wind Direction
KUUJUAQ ANN CLG .4% CONDNS DB=>MWB 74.84 18.72 60.26 Wetbulb [F] 9.62 210.0
KUUJUAQ ANN CLG .4% CONDNS WB=>MDB 71.78 18.72 62.42 Wetbulb [F] 9.62 210.0
KUUJUAQ ANN HTG 99.6% CONDNS DB -34.78 0.0 -34.78 Wetbulb [F] 4.47 220.0

Time Setpoint Not Met Time (hr)
During Heating 107.5
During Cooling 5.25
During Occupied Heating 107.5
During Occupied Cooling 5.0

Tolerance for Time Setpoint Not Met Temperature (F)
Heating 1.8
Cooling 1.8

Annual Overview

One or more tables in Annual Overview section returned false and was skipped.

End Use Consumption (kBtu)
Heating 2,927,096
Cooling 60,603
Interior Lighting 299,122
Exterior Lighting 0
Interior Equipment 468,544
Exterior Equipment 0
Fans 154,760
Pumps 1,346
Heat Rejection 38
Humidification 0
Heat Recovery 0
Water Systems 741,961
Refrigeration 0
Generators 0

Fuel Consumption (kBtu)
Electricity 4,653,479
Natural Gas 0
Additional Fuel 0
District Cooling 0
District Heating 0

End Use Consumption (kWh)
Heating 857,847
Cooling 17,761
Interior Lighting 87,664
Exterior Lighting 0
Interior Equipment 137,317
Exterior Equipment 0
Fans 45,356
Pumps 394
Heat Rejection 11
Humidification 0
Heat Recovery 0
Water Systems 217,447
Refrigeration 0
Generators 0

Monthly Overview


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total
Heating 137880.28 115110.0 111889.44 70708.33 47476.94 27969.72 18955.92 19656.92 33895.83 55555.83 84232.78 134514.44 857846.44
Cooling 7.67 95.88 263.04 1340.63 1047.37 3516.86 5632.64 4479.44 1257.05 104.76 11.77 4.89 17762.0
Interior Lighting 7444.64 6725.47 7454.72 7191.47 7454.72 7211.64 7434.56 7454.72 7201.56 7444.64 7211.64 7434.56 87664.33
Exterior Lighting
Interior Equipment 11662.0 10534.06 11666.97 11279.42 11666.97 11289.33 11657.06 11666.97 11284.39 11662.0 11289.33 11657.06 137315.56
Exterior Equipment
Fans 3235.72 2961.44 3346.19 3697.72 3678.78 4614.5 5517.86 5015.42 3651.44 3271.39 3135.08 3231.08 45356.64
Pumps 18.81 17.62 22.94 33.98 44.25 45.11 45.7 47.2 40.88 39.28 21.33 17.08 394.17
Heat Rejection 0.01 0.01 0.01 0.4 0.48 1.73 3.73 3.28 0.67 0.1 0.03 0.01 10.45
Humidification
Heat Recovery 0.26 0.53 0.79
Water Systems 18416.42 16733.44 18570.33 17862.14 18571.17 17957.17 18470.03 18386.92 17748.44 18303.64 17955.56 18473.25 217448.5
Refrigeration
Generators
Total 178665.55 152177.93 153213.64 112114.09 89940.69 72606.06 67717.74 66711.4 75080.27 96381.64 123857.52 175332.36 1363798.88

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Heating 342.8094 300.1314 306.61 218.4302 81.2517 31.3961 41.171 54.9863 67.858 147.6764 237.5473 321.343
Cooling 5.7068 18.7255 11.6458 4.5415 0.2981
Interior Lighting 21.5307 21.5307 21.5307 37.5581 37.2956 37.2956 37.2956 37.5581 37.2956 21.5307 21.5307 21.5307
Exterior Lighting
Interior Equipment 28.4158 28.4158 28.4158 31.5707 31.5045 31.5045 31.5045 31.5707 31.5045 28.4158 28.4158 28.4158
Exterior Equipment
Fans 4.554 4.554 4.554 4.2346 6.7233 12.4119 9.2927 6.4278 4.3663 4.554 4.554 4.554
Pumps 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.1271 0.0172 0.0172 0.0172 0.0172
Heat Rejection 0.004
Humidification
Heat Recovery
Water Systems 63.1655 63.0269 55.9846 50.7739 59.0968 59.1043 59.0982 49.5786 58.8356 49.9055 40.805 63.1655
Refrigeration
Generators
Total 460.49 417.68 417.11 342.58 221.6 190.46 190.02 184.79 200.18 252.1 332.87 439.03

Utility Bills/Rates

No Data to Show for Utility Bills/Rates

Envelope


Construction Net Area (ft^2) Surface Count R Value (ft^2*h*R/Btu)
Customized opaque construction {3f23251b-1b6f-408d-b9ff-3e4801600185} to conductance of 0.142 8,435 9 39.99
Customized opaque construction {87f68ac4-9638-42b3-afae-d85ab9c2e112} to conductance of 0.183 33,185 140 31.03

Construction Area (ft^2) Surface Count U-Factor (Btu/ft^2*h*R)
Customized Fenestration: cond=0.160 tvis=0.220 tsol=0.232 8,311 140 0.2818

Description Total (%) North (%) East (%) South (%) West (%)
Gross Window-Wall Ratio 20.03 20.13 19.88 20.13 19.59
Gross Window-Wall Ratio (Conditioned) 20.03 20.13 19.88 20.13 19.59
Skylight-Roof Ratio 0.0

Space Type Breakdown


Space Type Name Floor Area (ft^2) Standards Building Type Standards Space Type
Space Function Corr. < 2.4m wide-sch-G 8,359 Space Function Corr. < 2.4m wide-sch-G
Space Function Dwelling Unit(s) 75,042 Space Function Dwelling Unit(s)
Space Function Office - enclosed 950 Space Function Office - enclosed

Space Type Summary


Definition Value Unit Inst. Multiplier
Space Function Corr. < 2.4m wide-sch-G People Definition 0.0009 people/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Lights Definition 0.7804 W/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Ventilation (outdoor air method Sum) 0.0600 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Dwelling Unit(s) People Definition 0.0016 people/ft^2 1.0
Space Function Dwelling Unit(s) Elec Equip Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Lights Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Ventilation (outdoor air method Sum) 0.0680 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Office - enclosed People Definition 0.0046 people/ft^2 1.0
Space Function Office - enclosed Elec Equip Definition 0.6968 W/ft^2 1.0
Space Function Office - enclosed Lights Definition 1.1055 W/ft^2 1.0
Space Function Office - enclosed Ventilation (outdoor air method Sum) 0.0850 cfm/floor area ft^2

Interior Lighting Summary


Zone Lighting Power Density (W/ft^2) Total Power (W) Schedule Name Scheduled Hours/Week (hr) Actual Load Hours/Week (hr) Return Air Fraction Annual Consumption (kWh)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 1.11 1050.15 NECB-A-LIGHTING 56.27 56.27 0.0000 3080.56

Plug Loads Summary


Electricity Annual Value (kWh)
InteriorEquipment:Electricity:Zone:SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2450.0

Exterior Lighting

No Data to Show for Exterior Lighting

Water Use Equipment


Instance Plant Loop Definition Space Peak Flow Rate (gal/min) Flow Rate Schedule Target Temp Range (F)
F2 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n1 apartment Service Water Use Def 0.06gal/min F2 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n2 apartment Service Water Use Def 0.06gal/min F2 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F2 ne apartment Service Water Use Def 0.06gal/min F2 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 nw apartment Service Water Use Def 0.06gal/min F2 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s1 apartment Service Water Use Def 0.06gal/min F2 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s2 apartment Service Water Use Def 0.06gal/min F2 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 se apartment Service Water Use 0.06gal/min Main Service Water Loop F2 se apartment Service Water Use Def 0.06gal/min F2 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 sw apartment Service Water Use Def 0.06gal/min F2 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n1 apartment Service Water Use Def 0.06gal/min F3 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n2 apartment Service Water Use Def 0.06gal/min F3 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F3 ne apartment Service Water Use Def 0.06gal/min F3 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 nw apartment Service Water Use Def 0.06gal/min F3 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s1 apartment Service Water Use Def 0.06gal/min F3 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s2 apartment Service Water Use Def 0.06gal/min F3 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 se apartment Service Water Use 0.06gal/min Main Service Water Loop F3 se apartment Service Water Use Def 0.06gal/min F3 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 sw apartment Service Water Use Def 0.06gal/min F3 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n1 apartment Service Water Use Def 0.06gal/min F4 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n2 apartment Service Water Use Def 0.06gal/min F4 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F4 ne apartment Service Water Use Def 0.06gal/min F4 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 nw apartment Service Water Use Def 0.06gal/min F4 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s1 apartment Service Water Use Def 0.06gal/min F4 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s2 apartment Service Water Use Def 0.06gal/min F4 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 se apartment Service Water Use 0.06gal/min Main Service Water Loop F4 se apartment Service Water Use Def 0.06gal/min F4 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 sw apartment Service Water Use Def 0.06gal/min F4 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n1 apartment Service Water Use Def 0.06gal/min F6 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n2 apartment Service Water Use Def 0.06gal/min F6 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F6 ne apartment Service Water Use Def 0.06gal/min F6 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 nw apartment Service Water Use Def 0.06gal/min F6 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s1 apartment Service Water Use Def 0.06gal/min F6 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s2 apartment Service Water Use Def 0.06gal/min F6 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 se apartment Service Water Use 0.06gal/min Main Service Water Loop F6 se apartment Service Water Use Def 0.06gal/min F6 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 sw apartment Service Water Use Def 0.06gal/min F6 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n1 apartment Service Water Use Def 0.06gal/min F7 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n2 apartment Service Water Use Def 0.06gal/min F7 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F7 ne apartment Service Water Use Def 0.06gal/min F7 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 nw apartment Service Water Use Def 0.06gal/min F7 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s1 apartment Service Water Use Def 0.06gal/min F7 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s2 apartment Service Water Use Def 0.06gal/min F7 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 se apartment Service Water Use 0.06gal/min Main Service Water Loop F7 se apartment Service Water Use Def 0.06gal/min F7 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 sw apartment Service Water Use Def 0.06gal/min F7 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n1 apartment Service Water Use Def 0.06gal/min F8 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n2 apartment Service Water Use Def 0.06gal/min F8 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F8 ne apartment Service Water Use Def 0.06gal/min F8 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 nw apartment Service Water Use Def 0.06gal/min F8 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s1 apartment Service Water Use Def 0.06gal/min F8 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s2 apartment Service Water Use Def 0.06gal/min F8 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 se apartment Service Water Use 0.06gal/min Main Service Water Loop F8 se apartment Service Water Use Def 0.06gal/min F8 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 sw apartment Service Water Use Def 0.06gal/min F8 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n1 apartment Service Water Use Def 0.06gal/min F9 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n2 apartment Service Water Use Def 0.06gal/min F9 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F9 ne apartment Service Water Use Def 0.06gal/min F9 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 nw apartment Service Water Use Def 0.06gal/min F9 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s1 apartment Service Water Use Def 0.06gal/min F9 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s2 apartment Service Water Use Def 0.06gal/min F9 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 se apartment Service Water Use 0.06gal/min Main Service Water Loop F9 se apartment Service Water Use Def 0.06gal/min F9 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 sw apartment Service Water Use Def 0.06gal/min F9 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n1 apartment Service Water Use 0.06gal/min Main Service Water Loop G n1 apartment Service Water Use Def 0.06gal/min G N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n2 apartment Service Water Use 0.06gal/min Main Service Water Loop G n2 apartment Service Water Use Def 0.06gal/min G N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G ne apartment Service Water Use 0.06gal/min Main Service Water Loop G ne apartment Service Water Use Def 0.06gal/min G NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G nw apartment Service Water Use 0.06gal/min Main Service Water Loop G nw apartment Service Water Use Def 0.06gal/min G NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s1 apartment Service Water Use 0.06gal/min Main Service Water Loop G s1 apartment Service Water Use Def 0.06gal/min G S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s2 apartment Service Water Use 0.06gal/min Main Service Water Loop G s2 apartment Service Water Use Def 0.06gal/min G S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G sw apartment Service Water Use 0.06gal/min Main Service Water Loop G sw apartment Service Water Use Def 0.06gal/min G SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n1 apartment Service Water Use 0.06gal/min Main Service Water Loop M n1 apartment Service Water Use Def 0.06gal/min M N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n2 apartment Service Water Use 0.06gal/min Main Service Water Loop M n2 apartment Service Water Use Def 0.06gal/min M N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M ne apartment Service Water Use 0.06gal/min Main Service Water Loop M ne apartment Service Water Use Def 0.06gal/min M NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M nw apartment Service Water Use 0.06gal/min Main Service Water Loop M nw apartment Service Water Use Def 0.06gal/min M NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s1 apartment Service Water Use 0.06gal/min Main Service Water Loop M s1 apartment Service Water Use Def 0.06gal/min M S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s2 apartment Service Water Use 0.06gal/min Main Service Water Loop M s2 apartment Service Water Use Def 0.06gal/min M S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M se apartment Service Water Use 0.06gal/min Main Service Water Loop M se apartment Service Water Use Def 0.06gal/min M SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M sw apartment Service Water Use 0.06gal/min Main Service Water Loop M sw apartment Service Water Use Def 0.06gal/min M SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
Office Service Water Use 0.03gal/min Main Service Water Loop Office Service Water Use Def 0.03gal/min Office 0.03 NECB-A-Service Water Heating 140.0 to 140.0
T n1 apartment Service Water Use 0.06gal/min Main Service Water Loop T n1 apartment Service Water Use Def 0.06gal/min T N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T n2 apartment Service Water Use 0.06gal/min Main Service Water Loop T n2 apartment Service Water Use Def 0.06gal/min T N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T ne apartment Service Water Use 0.06gal/min Main Service Water Loop T ne apartment Service Water Use Def 0.06gal/min T NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T nw apartment Service Water Use 0.06gal/min Main Service Water Loop T nw apartment Service Water Use Def 0.06gal/min T NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s1 apartment Service Water Use 0.06gal/min Main Service Water Loop T s1 apartment Service Water Use Def 0.06gal/min T S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s2 apartment Service Water Use 0.06gal/min Main Service Water Loop T s2 apartment Service Water Use Def 0.06gal/min T S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T se apartment Service Water Use 0.06gal/min Main Service Water Loop T se apartment Service Water Use Def 0.06gal/min T SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T sw apartment Service Water Use 0.06gal/min Main Service Water Loop T sw apartment Service Water Use Def 0.06gal/min T SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0

HVAC Load Profiles


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Average Outdoor Air Dry Bulb (F) -5.3 -5.4 -2.2 16.0 31.5 44.3 51.8 51.4 40.4 30.6 17.3 -1.8
Cooling Load (MBtu) 0.03 0.33 0.9 4.57 3.57 12.0 19.22 15.28 4.29 0.36 0.04 0.02
Heating Load (MBtu) 470.47 392.77 381.78 241.27 162.0 95.44 64.68 67.07 115.66 189.56 287.41 458.98

Zone Conditions


Zone Unmet Htg (hr) Unmet Htg - Occ (hr) < 56 (F) 56-61 (F) 61-66 (F) 66-68 (F) 68-70 (F) 70-72 (F) 72-74 (F) 74-76 (F) 76-78 (F) 78-83 (F) 83-88 (F) >= 88 (F) Unmet Clg (hr) Unmet Clg - Occ (hr) Mean Temp (F)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 26 502 2775 1378 4079 0 0 0 0 0 0 73.1 (F)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 21 303 677 3472 951 3336 0 0 0 0 0 0 72.5 (F)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 21 303 676 3466 955 3339 0 0 0 0 0 0 72.5 (F)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 288 477 509 3578 1065 2843 0 0 0 0 0 0 72.2 (F)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 283 470 527 3583 1094 2803 0 0 0 0 0 0 72.2 (F)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 11 137 422 1982 1265 4943 0 0 0 0 0 0 73.4 (F)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 11 142 417 1972 1260 4958 0 0 0 0 0 0 73.4 (F)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 193 341 425 2528 1104 4169 0 0 0 0 0 0 72.8 (F)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 175 342 467 2609 1164 4003 0 0 0 0 0 0 72.8 (F)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 30 506 2809 1352 4063 0 0 0 0 0 0 73.1 (F)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 30 320 678 3483 942 3307 0 0 0 0 0 0 72.5 (F)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 30 321 678 3483 941 3307 0 0 0 0 0 0 72.5 (F)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 318 472 493 3633 1062 2782 0 0 0 0 0 0 72.1 (F)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 317 463 515 3618 1085 2762 0 0 0 0 0 0 72.1 (F)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 18 149 428 2034 1243 4888 0 0 0 0 0 0 73.4 (F)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 18 150 427 2029 1244 4892 0 0 0 0 0 0 73.4 (F)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 192 353 450 2644 1113 4008 0 0 0 0 0 0 72.8 (F)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 188 358 460 2668 1141 3945 0 0 0 0 0 0 72.7 (F)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 36 523 2840 1362 3999 0 0 0 0 0 0 73.1 (F)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 47 331 676 3520 965 3221 0 0 0 0 0 0 72.5 (F)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 47 332 674 3515 964 3228 0 0 0 0 0 0 72.5 (F)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 341 484 479 3679 1089 2688 0 0 0 0 0 0 72.1 (F)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 346 474 504 3660 1113 2663 0 0 0 0 0 0 72.1 (F)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 24 163 436 2096 1250 4791 0 0 0 0 0 0 73.3 (F)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 24 162 438 2091 1252 4793 0 0 0 0 0 0 73.3 (F)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 212 354 471 2716 1162 3845 0 0 0 0 0 0 72.7 (F)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 211 358 475 2742 1162 3812 0 0 0 0 0 0 72.7 (F)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 55 558 2944 1375 3828 0 0 0 0 0 0 73.0 (F)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 75 366 674 3641 1002 3002 0 0 0 0 0 0 72.4 (F)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 74 368 671 3640 1008 2999 0 0 0 0 0 0 72.4 (F)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 392 479 477 3798 1123 2491 0 0 0 0 0 0 71.9 (F)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 393 482 496 3787 1131 2471 0 0 0 0 0 0 71.9 (F)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 41 180 469 2234 1270 4566 0 0 0 0 0 0 73.2 (F)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 41 179 469 2235 1273 4563 0 0 0 0 0 0 73.2 (F)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 263 360 473 2884 1218 3562 0 0 0 0 0 0 72.5 (F)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 262 359 483 2891 1206 3559 0 0 0 0 0 0 72.5 (F)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 66 586 3005 1444 3659 0 0 0 0 0 0 72.9 (F)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 85 388 674 3698 1087 2828 0 0 0 0 0 0 72.3 (F)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 85 390 675 3687 1089 2834 0 0 0 0 0 0 72.3 (F)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 417 483 476 3886 1155 2343 0 0 0 0 0 0 71.9 (F)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 415 488 495 3862 1166 2334 0 0 0 0 0 0 71.9 (F)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 46 199 485 2327 1299 4404 0 0 0 0 0 0 73.1 (F)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 46 199 485 2329 1299 4402 0 0 0 0 0 0 73.1 (F)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 281 371 475 2984 1254 3395 0 0 0 0 0 0 72.5 (F)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 282 375 472 2981 1246 3404 0 0 0 0 0 0 72.5 (F)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 80 623 3192 1512 3353 0 0 0 0 0 0 72.8 (F)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 98 422 677 3813 1267 2483 0 0 0 0 0 0 72.2 (F)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 98 424 675 3810 1265 2488 0 0 0 0 0 0 72.2 (F)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 454 489 477 4021 1224 2095 0 0 0 0 0 0 71.8 (F)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 448 494 496 4007 1205 2110 0 0 0 0 0 0 71.8 (F)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 56 227 518 2480 1409 4070 0 0 0 0 0 0 73.0 (F)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 56 227 516 2484 1413 4064 0 0 0 0 0 0 73.0 (F)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 316 382 478 3128 1340 3116 0 0 0 0 0 0 72.3 (F)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 313 381 481 3131 1322 3132 0 0 0 0 0 0 72.3 (F)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0 0 0 0 4 151 727 3590 1743 2545 0 0 0 0 0 0 72.5 (F)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 170 463 690 4067 1445 1925 0 0 0 0 0 0 71.9 (F)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 171 461 693 4068 1443 1924 0 0 0 0 0 0 71.9 (F)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 2 2 0 0 532 518 470 4344 1175 1721 0 0 0 0 0 0 71.5 (F)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1 1 0 0 527 527 469 4333 1158 1746 0 0 0 0 0 0 71.5 (F)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 90 323 563 2852 1681 3251 0 0 0 0 0 0 72.6 (F)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 90 323 566 2854 1677 3250 0 0 0 0 0 0 72.6 (F)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 401 432 476 3472 1423 2556 0 0 0 0 0 0 72.0 (F)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 403 432 481 3444 1397 2603 0 0 0 0 0 0 72.1 (F)
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 117 596 2702 1470 3875 0 0 0 0 0 0 73.0 (F)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 20 349 674 3442 1097 3178 0 0 0 0 0 0 72.5 (F)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 19 352 670 3433 1090 3196 0 0 0 0 0 0 72.5 (F)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 323 468 492 3560 1127 2790 0 0 0 0 0 0 72.1 (F)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 323 464 519 3541 1152 2761 0 0 0 0 0 0 72.1 (F)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 12 169 448 1992 1357 4782 0 0 0 0 0 0 73.3 (F)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 14 181 446 1955 1331 4833 0 0 0 0 0 0 73.3 (F)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 199 358 482 2534 1280 3907 0 0 0 0 0 0 72.7 (F)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 43 545 2894 1362 3916 0 0 0 0 0 0 73.0 (F)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 58 356 662 3595 957 3132 0 0 0 0 0 0 72.4 (F)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 58 357 662 3589 956 3138 0 0 0 0 0 0 72.4 (F)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 368 488 474 3729 1100 2601 0 0 0 0 0 0 72.0 (F)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 367 482 503 3715 1119 2574 0 0 0 0 0 0 72.0 (F)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 32 165 461 2169 1264 4669 0 0 0 0 0 0 73.3 (F)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 32 165 461 2172 1260 4670 0 0 0 0 0 0 73.3 (F)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 240 354 471 2800 1194 3701 0 0 0 0 0 0 72.6 (F)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 237 357 475 2819 1189 3683 0 0 0 0 0 0 72.6 (F)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 0 0 0 0 677 506 639 1716 1219 3020 492 420 71 0 5 5 72.8 (F)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 11 11 0 0 879 460 522 4646 1009 1244 0 0 0 0 0 0 71.1 (F)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 105 105 0 0 1111 528 425 4932 773 991 0 0 0 0 0 0 70.7 (F)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 106 106 0 0 1109 526 427 4939 764 995 0 0 0 0 0 0 70.7 (F)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 93 93 0 5 1265 438 387 4973 648 1044 0 0 0 0 0 0 70.7 (F)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 88 88 0 5 1283 465 393 4899 695 1020 0 0 0 0 0 0 70.6 (F)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 61 61 0 0 1024 458 458 4232 1042 1546 0 0 0 0 0 0 71.1 (F)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 61 61 0 0 1024 453 459 4238 1039 1547 0 0 0 0 0 0 71.1 (F)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 61 61 0 1 1180 435 380 4464 827 1473 0 0 0 0 0 0 70.9 (F)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 61 61 0 1 1188 475 390 4364 856 1486 0 0 0 0 0 0 70.9 (F)

Zone < 30 (%) 30-35 (%) 35-40 (%) 40-45 (%) 45-50 (%) 50-55 (%) 55-60 (%) 60-65 (%) 65-70 (%) 70-75 (%) 75-80 (%) >= 80 (%) Mean Relative Humidity (%)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 7383 697 359 267 52 2 0 0 0 0 0 0 17.3 (%)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 5547 1190 964 551 319 158 31 0 0 0 0 0 26.1 (%)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 5546 1194 966 546 318 158 31 1 0 0 0 0 26.1 (%)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 5580 1137 959 582 321 159 22 0 0 0 0 0 25.8 (%)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 5597 1147 971 559 319 147 20 0 0 0 0 0 25.7 (%)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5706 1174 904 563 284 123 6 0 0 0 0 0 25.3 (%)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5710 1172 905 563 283 122 5 0 0 0 0 0 25.3 (%)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5748 1142 923 569 271 104 3 0 0 0 0 0 25.1 (%)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5723 1152 935 537 299 107 7 0 0 0 0 0 25.1 (%)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 7386 697 359 267 49 2 0 0 0 0 0 0 17.3 (%)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 5577 1203 945 535 318 155 27 0 0 0 0 0 25.9 (%)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 5575 1203 946 536 317 155 27 1 0 0 0 0 25.9 (%)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 5624 1136 951 558 311 159 21 0 0 0 0 0 25.6 (%)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 5640 1147 954 544 314 143 18 0 0 0 0 0 25.5 (%)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5737 1163 903 556 278 118 5 0 0 0 0 0 25.2 (%)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5738 1165 895 557 281 119 5 0 0 0 0 0 25.2 (%)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5775 1128 901 566 273 113 4 0 0 0 0 0 25.0 (%)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5771 1136 925 530 285 107 6 0 0 0 0 0 24.9 (%)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 7386 696 360 266 50 2 0 0 0 0 0 0 17.3 (%)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 5591 1197 942 532 318 152 28 0 0 0 0 0 25.8 (%)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 5590 1201 937 533 316 154 28 1 0 0 0 0 25.8 (%)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 5658 1119 950 544 311 155 23 0 0 0 0 0 25.4 (%)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 5672 1133 944 536 315 143 17 0 0 0 0 0 25.4 (%)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5754 1164 893 550 276 118 5 0 0 0 0 0 25.1 (%)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5755 1162 887 552 281 118 5 0 0 0 0 0 25.1 (%)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5794 1115 899 558 273 117 4 0 0 0 0 0 24.9 (%)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5800 1119 923 520 287 105 6 0 0 0 0 0 24.8 (%)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 7380 698 358 267 55 2 0 0 0 0 0 0 17.3 (%)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 5593 1191 938 537 316 154 31 0 0 0 0 0 25.8 (%)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 5591 1192 937 538 316 155 30 1 0 0 0 0 25.8 (%)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 5680 1109 944 536 309 158 24 0 0 0 0 0 25.3 (%)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 5696 1119 941 524 319 142 19 0 0 0 0 0 25.2 (%)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5761 1166 886 543 279 120 5 0 0 0 0 0 25.0 (%)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5763 1162 881 549 278 122 5 0 0 0 0 0 25.0 (%)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5820 1100 894 547 275 120 4 0 0 0 0 0 24.7 (%)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5833 1106 910 512 284 108 7 0 0 0 0 0 24.7 (%)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 7375 695 361 267 60 2 0 0 0 0 0 0 17.4 (%)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 5582 1176 952 542 321 155 32 0 0 0 0 0 25.8 (%)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 5578 1185 951 534 321 158 32 1 0 0 0 0 25.8 (%)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 5675 1095 953 544 309 159 25 0 0 0 0 0 25.3 (%)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 5691 1110 942 531 321 145 20 0 0 0 0 0 25.2 (%)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5754 1165 886 542 285 123 5 0 0 0 0 0 25.0 (%)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5752 1163 888 544 283 125 5 0 0 0 0 0 25.0 (%)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5822 1095 894 542 281 121 5 0 0 0 0 0 24.7 (%)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5833 1100 909 510 291 110 7 0 0 0 0 0 24.7 (%)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 7340 722 357 276 63 2 0 0 0 0 0 0 17.4 (%)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 5542 1154 984 550 330 163 36 1 0 0 0 0 25.9 (%)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 5543 1154 980 555 327 164 35 2 0 0 0 0 25.9 (%)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 5650 1088 957 552 323 156 34 0 0 0 0 0 25.3 (%)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 5668 1099 955 533 328 149 28 0 0 0 0 0 25.3 (%)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5724 1151 911 546 288 132 8 0 0 0 0 0 25.1 (%)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5724 1147 906 554 290 132 7 0 0 0 0 0 25.1 (%)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5794 1097 898 548 291 125 7 0 0 0 0 0 24.8 (%)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5805 1102 914 513 304 114 8 0 0 0 0 0 24.7 (%)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 7244 796 353 289 72 6 0 0 0 0 0 0 17.6 (%)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 5468 1129 969 618 355 169 49 3 0 0 0 0 26.1 (%)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 5466 1134 966 616 358 168 49 3 0 0 0 0 26.1 (%)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 5593 1093 948 580 341 163 42 0 0 0 0 0 25.5 (%)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 5606 1093 941 583 344 154 39 0 0 0 0 0 25.4 (%)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 5635 1135 939 571 321 143 16 0 0 0 0 0 25.4 (%)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 5634 1136 935 573 320 146 16 0 0 0 0 0 25.4 (%)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 5738 1079 921 562 311 132 17 0 0 0 0 0 25.0 (%)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 5752 1083 939 527 315 128 16 0 0 0 0 0 24.9 (%)
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 7358 703 360 275 62 2 0 0 0 0 0 0 17.4 (%)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 5453 1191 1000 566 341 168 40 1 0 0 0 0 26.5 (%)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 5452 1197 990 570 341 168 40 2 0 0 0 0 26.5 (%)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 5439 1167 1000 603 349 168 34 0 0 0 0 0 26.3 (%)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 5451 1192 988 595 349 151 34 0 0 0 0 0 26.3 (%)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 5606 1160 941 589 311 140 13 0 0 0 0 0 25.7 (%)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 5617 1156 948 588 307 134 10 0 0 0 0 0 25.7 (%)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 5603 1167 969 574 315 120 12 0 0 0 0 0 25.6 (%)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 7383 698 358 266 53 2 0 0 0 0 0 0 17.3 (%)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 5600 1188 938 536 316 152 30 0 0 0 0 0 25.8 (%)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 5597 1189 937 535 317 156 28 1 0 0 0 0 25.8 (%)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 5682 1100 951 539 309 156 23 0 0 0 0 0 25.4 (%)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 5689 1126 940 529 316 141 19 0 0 0 0 0 25.3 (%)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5760 1161 892 543 281 118 5 0 0 0 0 0 25.1 (%)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5761 1158 888 547 280 121 5 0 0 0 0 0 25.1 (%)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5813 1104 894 553 273 119 4 0 0 0 0 0 24.8 (%)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5823 1110 915 514 284 107 7 0 0 0 0 0 24.7 (%)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 4759 1122 1129 1148 598 4 0 0 0 0 0 0 29.2 (%)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 7056 864 397 280 136 26 1 0 0 0 0 0 17.8 (%)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 5754 970 941 523 317 190 62 3 0 0 0 0 24.4 (%)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 5756 969 940 518 321 189 64 3 0 0 0 0 24.4 (%)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 5834 960 901 513 309 174 66 3 0 0 0 0 24.0 (%)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 5832 974 916 502 317 155 63 1 0 0 0 0 24.0 (%)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5853 975 904 516 299 174 38 1 0 0 0 0 24.0 (%)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5851 974 903 518 300 175 38 1 0 0 0 0 24.0 (%)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5915 948 878 515 293 163 47 1 0 0 0 0 23.7 (%)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5919 968 887 485 323 136 41 1 0 0 0 0 23.7 (%)

Zone Overview


Area (ft^2) Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume (ft^3) Multiplier Above Ground Gross Wall Area (ft^2) Underground Gross Wall Area (ft^2) Window Glass Area (ft^2) Lighting (W/ft^2) People (ft^2/person) Plug and Process (W/ft^2)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 32.29 0.78 1075.31 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 1.11 215.06 0.7
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 16.15 0.78 1075.31 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 76.53 0.46 645.19 0.46
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 126.8 0.46 645.19 0.46
Total 84351.17 843456.88 41495.09 0.0 8310.49 0.5 656.38 0.42
Conditioned Total 84351.17 843456.88 41495.09 0.0 8310.49 0.5 656.38 0.42
Unconditioned Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Not Part of Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Heating/Cooling Calculated Design Load Design Load With Sizing Factor Calculated Design Air Flow (ft^3/min) Design Air Flow With Sizing Factor (ft^3/min) Date/Time Of Peak Outdoor Temperature at Peak Load (F) Outdoor Humidity Ratio at Peak Load (lbWater/lbAir)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 167.39 182.22 7/21 20:00:00 65.48 0.01
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Heating 4.25 (kBtu/h) 5.52 (kBtu/h) 103.83 133.49 1/21 09:30:00 -34.78 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 3.99 (kBtu/h) 5.18 (kBtu/h) 95.35 125.01 1/21 09:30:00 -34.78 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 3.98 (kBtu/h) 5.18 (kBtu/h) 95.35 125.01 1/21 09:30:00 -34.78 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 230.96 254.27 7/21 08:45:00 63.66 0.01
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 6.39 (kBtu/h) 8.3 (kBtu/h) 154.68 201.29 1/21 09:30:00 -34.78 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 230.96 254.27 7/21 19:30:00 66.51 0.01
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 6.41 (kBtu/h) 8.33 (kBtu/h) 154.68 201.29 1/21 09:30:00 -34.78 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.47 (ton) 235.2 258.5 7/21 13:00:00 73.9 0.01
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 4.03 (kBtu/h) 5.24 (kBtu/h) 97.47 127.13 1/21 09:30:00 -34.78 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 239.43 262.74 7/21 13:00:00 73.9 0.01
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 4.04 (kBtu/h) 5.25 (kBtu/h) 97.47 127.13 1/21 09:30:00 -34.78 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.64 (ton) 322.07 353.85 7/21 12:45:00 73.53 0.01
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 6.45 (kBtu/h) 8.39 (kBtu/h) 156.8 203.41 1/21 09:30:00 -34.78 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.6 (ton) 300.88 330.55 7/21 16:45:00 72.59 0.01
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 6.45 (kBtu/h) 8.38 (kBtu/h) 156.8 203.41 1/21 09:30:00 -34.78 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 182.22 7/21 20:00:00 65.48 0.01
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Heating 4.2 (kBtu/h) 5.46 (kBtu/h) 101.71 131.37 1/21 09:30:00 -34.78 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 4.03 (kBtu/h) 5.24 (kBtu/h) 97.47 127.13 1/21 09:30:00 -34.78 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 4.03 (kBtu/h) 5.23 (kBtu/h) 97.47 127.13 1/21 09:30:00 -34.78 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 230.96 254.27 7/21 08:45:00 63.66 0.01
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 6.48 (kBtu/h) 8.43 (kBtu/h) 156.8 203.41 1/21 09:30:00 -34.78 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 230.96 254.27 7/21 19:30:00 66.51 0.01
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 6.51 (kBtu/h) 8.46 (kBtu/h) 156.8 205.53 1/21 09:30:00 -34.78 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.47 (ton) 235.2 258.5 7/21 13:00:00 73.9 0.01
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 4.08 (kBtu/h) 5.3 (kBtu/h) 99.59 127.13 1/21 09:30:00 -34.78 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 237.31 260.62 7/21 13:00:00 73.9 0.01
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 4.08 (kBtu/h) 5.3 (kBtu/h) 99.59 127.13 1/21 09:30:00 -34.78 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.61 (ton) 307.24 336.9 7/21 12:45:00 73.53 0.01
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 6.53 (kBtu/h) 8.48 (kBtu/h) 156.8 205.53 1/21 09:30:00 -34.78 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.6 (ton) 300.88 330.55 7/21 16:45:00 72.59 0.01
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 6.55 (kBtu/h) 8.51 (kBtu/h) 158.92 205.53 1/21 09:30:00 -34.78 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 182.22 7/21 20:00:00 65.48 0.01
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Heating 4.23 (kBtu/h) 5.5 (kBtu/h) 101.71 133.49 1/21 09:30:00 -34.78 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 4.1 (kBtu/h) 5.33 (kBtu/h) 99.59 129.25 1/21 09:30:00 -34.78 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 4.1 (kBtu/h) 5.33 (kBtu/h) 99.59 129.25 1/21 09:30:00 -34.78 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 230.96 252.15 7/21 08:45:00 63.66 0.01
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 6.59 (kBtu/h) 8.56 (kBtu/h) 158.92 207.65 1/21 09:30:00 -34.78 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 228.84 252.15 7/21 19:30:00 66.51 0.01
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 6.61 (kBtu/h) 8.6 (kBtu/h) 158.92 207.65 1/21 09:30:00 -34.78 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.47 (ton) 235.2 258.5 7/21 13:00:00 73.9 0.01
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 4.15 (kBtu/h) 5.4 (kBtu/h) 99.59 131.37 1/21 09:30:00 -34.78 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 237.31 260.62 7/21 13:00:00 73.9 0.01
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 4.15 (kBtu/h) 5.4 (kBtu/h) 99.59 131.37 1/21 09:30:00 -34.78 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.61 (ton) 305.12 334.78 7/21 12:45:00 73.53 0.01
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 6.63 (kBtu/h) 8.62 (kBtu/h) 161.03 207.65 1/21 09:30:00 -34.78 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.6 (ton) 300.88 330.55 7/21 16:45:00 72.59 0.01
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 6.66 (kBtu/h) 8.65 (kBtu/h) 161.03 209.77 1/21 09:30:00 -34.78 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 180.1 7/21 20:00:00 65.48 0.01
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Heating 4.3 (kBtu/h) 5.59 (kBtu/h) 103.83 135.61 1/21 09:30:00 -34.78 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 4.24 (kBtu/h) 5.51 (kBtu/h) 101.71 133.49 1/21 09:30:00 -34.78 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 4.24 (kBtu/h) 5.51 (kBtu/h) 101.71 133.49 1/21 09:30:00 -34.78 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 228.84 252.15 7/21 08:45:00 63.66 0.01
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 6.76 (kBtu/h) 8.79 (kBtu/h) 163.15 211.89 1/21 09:30:00 -34.78 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 228.84 252.15 7/21 19:30:00 66.51 0.01
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 6.79 (kBtu/h) 8.82 (kBtu/h) 163.15 214.01 1/21 09:30:00 -34.78 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.47 (ton) 235.2 258.5 7/21 13:00:00 73.9 0.01
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 4.29 (kBtu/h) 5.58 (kBtu/h) 103.83 135.61 1/21 09:30:00 -34.78 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 237.31 260.62 7/21 13:00:00 73.9 0.01
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 4.29 (kBtu/h) 5.58 (kBtu/h) 103.83 135.61 1/21 09:30:00 -34.78 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.6 (ton) 303.0 334.78 7/21 12:45:00 73.53 0.01
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 6.8 (kBtu/h) 8.84 (kBtu/h) 165.27 214.01 1/21 09:30:00 -34.78 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.59 (ton) 298.76 328.43 7/21 16:45:00 72.59 0.01
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 6.83 (kBtu/h) 8.88 (kBtu/h) 165.27 214.01 1/21 09:30:00 -34.78 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 180.1 7/21 20:00:00 65.48 0.01
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Heating 4.35 (kBtu/h) 5.66 (kBtu/h) 105.94 137.73 1/21 09:30:00 -34.78 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 4.31 (kBtu/h) 5.61 (kBtu/h) 103.83 135.61 1/21 09:30:00 -34.78 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 4.31 (kBtu/h) 5.61 (kBtu/h) 103.83 135.61 1/21 09:30:00 -34.78 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 08:45:00 63.66 0.01
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 6.84 (kBtu/h) 8.89 (kBtu/h) 165.27 216.13 1/21 09:30:00 -34.78 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 228.84 250.03 7/21 19:30:00 66.51 0.01
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 6.87 (kBtu/h) 8.93 (kBtu/h) 165.27 216.13 1/21 09:30:00 -34.78 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.47 (ton) 235.2 258.5 7/21 13:00:00 73.9 0.01
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 4.37 (kBtu/h) 5.68 (kBtu/h) 105.94 137.73 1/21 09:30:00 -34.78 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 237.31 260.62 7/21 13:00:00 73.9 0.01
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 4.37 (kBtu/h) 5.68 (kBtu/h) 105.94 137.73 1/21 09:30:00 -34.78 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.6 (ton) 303.0 332.66 7/21 12:45:00 73.53 0.01
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 6.89 (kBtu/h) 8.95 (kBtu/h) 167.39 216.13 1/21 09:30:00 -34.78 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.59 (ton) 298.76 328.43 7/21 16:45:00 72.59 0.01
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 6.92 (kBtu/h) 8.99 (kBtu/h) 167.39 218.24 1/21 09:30:00 -34.78 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 180.1 7/21 20:00:00 65.48 0.01
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Heating 4.49 (kBtu/h) 5.84 (kBtu/h) 108.06 141.96 1/21 09:30:00 -34.78 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 4.48 (kBtu/h) 5.83 (kBtu/h) 108.06 139.85 1/21 09:30:00 -34.78 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 4.48 (kBtu/h) 5.82 (kBtu/h) 108.06 139.85 1/21 09:30:00 -34.78 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 226.72 250.03 7/21 08:45:00 63.66 0.01
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.99 (kBtu/h) 9.09 (kBtu/h) 169.51 220.36 1/21 09:30:00 -34.78 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 228.84 250.03 7/21 19:30:00 66.51 0.01
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 7.02 (kBtu/h) 9.13 (kBtu/h) 169.51 220.36 1/21 09:30:00 -34.78 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.46 (ton) 233.08 256.38 7/21 13:00:00 73.9 0.01
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 4.54 (kBtu/h) 5.9 (kBtu/h) 110.18 141.96 1/21 09:30:00 -34.78 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 235.2 260.62 7/21 13:00:00 73.9 0.01
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 4.54 (kBtu/h) 5.9 (kBtu/h) 110.18 141.96 1/21 09:30:00 -34.78 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.6 (ton) 303.0 332.66 7/21 12:45:00 73.53 0.01
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 7.04 (kBtu/h) 9.15 (kBtu/h) 169.51 220.36 1/21 09:30:00 -34.78 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.59 (ton) 298.76 328.43 7/21 16:45:00 72.59 0.01
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 7.07 (kBtu/h) 9.19 (kBtu/h) 171.63 222.48 1/21 09:30:00 -34.78 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 167.39 184.34 7/21 20:00:00 65.48 0.01
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Heating 5.29 (kBtu/h) 6.88 (kBtu/h) 125.01 163.15 1/21 09:00:00 -34.78 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 148.32 163.15 7/21 20:00:00 65.48 0.01
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 5.21 (kBtu/h) 6.78 (kBtu/h) 127.13 163.15 1/21 09:30:00 -34.78 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 5.21 (kBtu/h) 6.78 (kBtu/h) 125.01 163.15 1/21 09:30:00 -34.78 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.45 (ton) 224.6 245.79 7/21 09:00:00 64.54 0.01
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 7.66 (kBtu/h) 9.96 (kBtu/h) 184.34 241.55 1/21 09:30:00 -34.78 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.42 (ton) 0.46 (ton) 233.08 256.38 7/21 19:30:00 66.51 0.01
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 7.69 (kBtu/h) 10.0 (kBtu/h) 186.46 241.55 1/21 09:30:00 -34.78 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 235.2 260.62 7/21 13:00:00 73.9 0.01
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 5.27 (kBtu/h) 6.85 (kBtu/h) 127.13 165.27 1/21 09:30:00 -34.78 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 239.43 262.74 7/21 13:00:00 73.9 0.01
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 5.27 (kBtu/h) 6.85 (kBtu/h) 127.13 165.27 1/21 09:30:00 -34.78 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.61 (ton) 305.12 336.9 7/21 12:45:00 73.53 0.01
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 7.71 (kBtu/h) 10.02 (kBtu/h) 186.46 241.55 1/21 09:30:00 -34.78 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.6 (ton) 303.0 334.78 7/21 16:45:00 72.59 0.01
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 7.74 (kBtu/h) 10.06 (kBtu/h) 186.46 243.67 1/21 09:30:00 -34.78 0.0
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN Cooling 0.31 (ton) 0.35 (ton) 173.75 190.7 7/21 09:00:00 64.54 0.01
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN Heating 4.54 (kBtu/h) 5.9 (kBtu/h) 110.18 141.96 1/21 09:30:00 -34.78 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.28 (ton) 141.96 154.68 7/21 20:00:00 65.48 0.01
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 3.95 (kBtu/h) 5.13 (kBtu/h) 95.35 125.01 1/21 09:30:00 -34.78 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.25 (ton) 0.27 (ton) 137.73 152.56 7/21 20:00:00 65.48 0.01
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 3.95 (kBtu/h) 5.13 (kBtu/h) 95.35 125.01 1/21 09:30:00 -34.78 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 256.38 281.81 7/21 08:30:00 62.76 0.01
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 6.17 (kBtu/h) 8.02 (kBtu/h) 148.32 194.94 1/21 09:30:00 -34.78 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.44 (ton) 0.49 (ton) 243.67 269.1 7/21 17:00:00 72.21 0.01
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 6.19 (kBtu/h) 8.05 (kBtu/h) 150.44 194.94 1/21 09:30:00 -34.78 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.47 (ton) 0.52 (ton) 260.62 286.05 7/21 12:45:00 73.53 0.01
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 3.99 (kBtu/h) 5.19 (kBtu/h) 97.47 125.01 1/21 09:30:00 -34.78 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.49 (ton) 0.53 (ton) 269.1 294.52 7/21 12:45:00 73.53 0.01
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 3.94 (kBtu/h) 5.12 (kBtu/h) 95.35 122.9 1/21 09:30:00 -34.78 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.58 (ton) 0.64 (ton) 319.95 351.73 7/21 15:00:00 74.84 0.01
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 6.23 (kBtu/h) 8.09 (kBtu/h) 150.44 194.94 1/21 09:30:00 -34.78 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Cooling 0.3 (ton) 0.33 (ton) 165.27 182.22 7/21 20:00:00 65.48 0.01
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Heating 4.27 (kBtu/h) 5.55 (kBtu/h) 103.83 133.49 1/21 09:30:00 -34.78 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.29 (ton) 146.2 161.03 7/21 20:00:00 65.48 0.01
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 4.17 (kBtu/h) 5.42 (kBtu/h) 101.71 131.37 1/21 09:30:00 -34.78 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 144.08 158.92 7/21 20:00:00 65.48 0.01
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 4.17 (kBtu/h) 5.42 (kBtu/h) 101.71 131.37 1/21 09:30:00 -34.78 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.46 (ton) 228.84 252.15 7/21 08:45:00 63.66 0.01
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 6.68 (kBtu/h) 8.68 (kBtu/h) 161.03 209.77 1/21 09:30:00 -34.78 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.41 (ton) 0.46 (ton) 228.84 252.15 7/21 19:30:00 66.51 0.01
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 6.71 (kBtu/h) 8.72 (kBtu/h) 163.15 209.77 1/21 09:30:00 -34.78 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.42 (ton) 0.47 (ton) 235.2 258.5 7/21 13:00:00 73.9 0.01
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 4.22 (kBtu/h) 5.49 (kBtu/h) 101.71 133.49 1/21 09:30:00 -34.78 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.43 (ton) 0.47 (ton) 237.31 260.62 7/21 13:00:00 73.9 0.01
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 4.22 (kBtu/h) 5.49 (kBtu/h) 101.71 133.49 1/21 09:30:00 -34.78 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.55 (ton) 0.6 (ton) 305.12 334.78 7/21 12:45:00 73.53 0.01
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 6.72 (kBtu/h) 8.74 (kBtu/h) 163.15 211.89 1/21 09:30:00 -34.78 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.54 (ton) 0.6 (ton) 298.76 330.55 7/21 16:45:00 72.59 0.01
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 6.75 (kBtu/h) 8.77 (kBtu/h) 163.15 211.89 1/21 09:30:00 -34.78 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Cooling 0.92 (ton) 1.01 (ton) 510.65 561.5 7/21 12:00:00 72.41 0.01
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Heating 7.36 (kBtu/h) 9.57 (kBtu/h) 173.75 226.72 1/21 08:00:00 -34.78 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.39 (ton) 194.94 214.01 7/21 14:30:00 74.84 0.01
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Heating 10.27 (kBtu/h) 13.35 (kBtu/h) 243.67 317.83 1/21 09:00:00 -34.78 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.28 (ton) 141.96 156.8 7/21 20:00:00 65.48 0.01
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 8.76 (kBtu/h) 11.38 (kBtu/h) 207.65 269.1 1/21 09:00:00 -34.78 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.25 (ton) 0.27 (ton) 137.73 152.56 7/21 20:00:00 65.48 0.01
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 8.75 (kBtu/h) 11.38 (kBtu/h) 207.65 269.1 1/21 09:00:00 -34.78 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.51 (ton) 0.56 (ton) 281.81 309.36 7/21 09:00:00 64.54 0.01
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 11.01 (kBtu/h) 14.32 (kBtu/h) 262.74 341.14 1/21 09:00:00 -34.78 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 294.52 322.07 7/21 16:30:00 72.97 0.01
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 11.04 (kBtu/h) 14.35 (kBtu/h) 262.74 341.14 1/21 09:00:00 -34.78 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 332.66 366.57 7/21 12:45:00 73.53 0.01
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 8.8 (kBtu/h) 11.44 (kBtu/h) 209.77 271.22 1/21 09:00:00 -34.78 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.67 (ton) 334.78 368.69 7/21 12:45:00 73.53 0.01
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 8.8 (kBtu/h) 11.44 (kBtu/h) 209.77 271.22 1/21 09:00:00 -34.78 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.76 (ton) 385.64 423.78 7/21 12:30:00 73.15 0.01
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 11.06 (kBtu/h) 14.37 (kBtu/h) 262.74 341.14 1/21 09:00:00 -34.78 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.69 (ton) 0.76 (ton) 385.64 423.78 7/21 14:30:00 74.84 0.01
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 11.08 (kBtu/h) 14.41 (kBtu/h) 262.74 343.26 1/21 09:00:00 -34.78 0.0

Zone Equipment Detail


Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Air Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:DX:SingleSpeed Autosized Btu/h Rated COP 3.39 COP
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 68.0 to 68.0 F
(demand)
Thermal Zones Total Floor Area 83,401 ft^2 89
Thermal Zones thermostat ranges for cooling 75.2 to 75.2 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:Uncontrolled 89
(controls)
HVAC Operation Schedule Make-up air unit Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting DifferentialEnthalpy Choice
Demand Controlled Ventilation Status false Bool

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:Water Autosized gal/min Plant Loop Chilled Water Loop
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:VariableVolume Autosized cfm Pressure Rise 5.85 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 55.4 to 55.4 F
(demand)
Thermal Zones Total Floor Area 950 ft^2 1
Thermal Zones thermostat ranges for cooling 75.2 to 95.0 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:VAV:Reheat 1
(controls)
HVAC Operation Schedule VAV with Reheat Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting NoEconomizer Choice
Demand Controlled Ventilation Status false Bool

Plant Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:Chiller:Electric:EIR 13,899.84 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
OS:SetpointManager:Scheduled Control Variable - Temperature 44.6 to 44.6 F
OS:Chiller:Electric:EIR 0.00 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
(demand)
OS:Coil:Cooling:Water Air Loop VAV with Reheat
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 44.60 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:CoolingTower:SingleSpeed - Air Autosized gal/min
OS:CoolingTower:SingleSpeed (cont) - Water Autosized cfm Fan Power at Design Air Flow Rate 158,224.72 W
OS:SetpointManager:Scheduled Control Variable - Temperature 84.2 to 84.2 F
(demand)
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 84.20 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:WaterHeater:Mixed 600 gal Heater Thermal Efficiency 1.00 fraction
OS:SetpointManager:Scheduled Control Variable - Temperature 140.0 to 140.0 F
(demand)
OS:WaterUse:Connections Water Use Connections 1
OS:WaterUse:Connections Water Use Connections 2
OS:WaterUse:Connections Water Use Connections 3
OS:WaterUse:Connections Water Use Connections 4
OS:WaterUse:Connections Water Use Connections 5
OS:WaterUse:Connections Water Use Connections 6
OS:WaterUse:Connections Water Use Connections 7
OS:WaterUse:Connections Water Use Connections 8
OS:WaterUse:Connections Water Use Connections 9
OS:WaterUse:Connections Water Use Connections 10
OS:WaterUse:Connections Water Use Connections 11
OS:WaterUse:Connections Water Use Connections 12
OS:WaterUse:Connections Water Use Connections 13
OS:WaterUse:Connections Water Use Connections 14
OS:WaterUse:Connections Water Use Connections 15
OS:WaterUse:Connections Water Use Connections 16
OS:WaterUse:Connections Water Use Connections 17
OS:WaterUse:Connections Water Use Connections 18
OS:WaterUse:Connections Water Use Connections 19
OS:WaterUse:Connections Water Use Connections 20
OS:WaterUse:Connections Water Use Connections 21
OS:WaterUse:Connections Water Use Connections 22
OS:WaterUse:Connections Water Use Connections 23
OS:WaterUse:Connections Water Use Connections 24
OS:WaterUse:Connections Water Use Connections 25
OS:WaterUse:Connections Water Use Connections 26
OS:WaterUse:Connections Water Use Connections 27
OS:WaterUse:Connections Water Use Connections 28
OS:WaterUse:Connections Water Use Connections 29
OS:WaterUse:Connections Water Use Connections 30
OS:WaterUse:Connections Water Use Connections 31
OS:WaterUse:Connections Water Use Connections 32
OS:WaterUse:Connections Water Use Connections 33
OS:WaterUse:Connections Water Use Connections 34
OS:WaterUse:Connections Water Use Connections 35
OS:WaterUse:Connections Water Use Connections 36
OS:WaterUse:Connections Water Use Connections 37
OS:WaterUse:Connections Water Use Connections 38
OS:WaterUse:Connections Water Use Connections 39
OS:WaterUse:Connections Water Use Connections 40
OS:WaterUse:Connections Water Use Connections 41
OS:WaterUse:Connections Water Use Connections 42
OS:WaterUse:Connections Water Use Connections 43
OS:WaterUse:Connections Water Use Connections 44
OS:WaterUse:Connections Water Use Connections 45
OS:WaterUse:Connections Water Use Connections 46
OS:WaterUse:Connections Water Use Connections 47
OS:WaterUse:Connections Water Use Connections 48
OS:WaterUse:Connections Water Use Connections 49
OS:WaterUse:Connections Water Use Connections 50
OS:WaterUse:Connections Water Use Connections 51
OS:WaterUse:Connections Water Use Connections 52
OS:WaterUse:Connections Water Use Connections 53
OS:WaterUse:Connections Water Use Connections 54
OS:WaterUse:Connections Water Use Connections 55
OS:WaterUse:Connections Water Use Connections 56
OS:WaterUse:Connections Water Use Connections 57
OS:WaterUse:Connections Water Use Connections 58
OS:WaterUse:Connections Water Use Connections 59
OS:WaterUse:Connections Water Use Connections 60
OS:WaterUse:Connections Water Use Connections 61
OS:WaterUse:Connections Water Use Connections 62
OS:WaterUse:Connections Water Use Connections 63
OS:WaterUse:Connections Water Use Connections 64
OS:WaterUse:Connections Water Use Connections 65
OS:WaterUse:Connections Water Use Connections 66
OS:WaterUse:Connections Water Use Connections 67
OS:WaterUse:Connections Water Use Connections 68
OS:WaterUse:Connections Water Use Connections 69
OS:WaterUse:Connections Water Use Connections 70
OS:WaterUse:Connections Water Use Connections 71
OS:WaterUse:Connections Water Use Connections 72
OS:WaterUse:Connections Water Use Connections 73
OS:WaterUse:Connections Water Use Connections 74
OS:WaterUse:Connections Water Use Connections 75
OS:WaterUse:Connections Water Use Connections 76
OS:WaterUse:Connections Water Use Connections 77
OS:WaterUse:Connections Water Use Connections 78
OS:WaterUse:Connections Water Use Connections 79
OS:WaterUse:Connections Water Use Connections 80
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 50.0 to 140.0 F
Design Loop Exit Temperature 140.00 F
Loop Design Temperature Difference 9.00 R

Outdoor Air


Average Number of Occupants Nominal Number of Occupants Zone Volume (ft^3) Avg. Mechanical Ventilation (ach) Min. Mechanical Ventilation (ach) Avg. Infiltration (ach) Min. Infiltration (ach) Avg. Simple Ventilation (ach) Min. Simple Ventilation (ach)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.39 0.35 0.015 0.0 0.0 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.433 0.396 0.046 0.0 0.0 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.434 0.396 0.046 0.0 0.0 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.431 0.394 0.076 0.0 0.0 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.432 0.394 0.076 0.0 0.0 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.448 0.396 0.046 0.0 0.0 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.448 0.396 0.046 0.0 0.0 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.445 0.395 0.076 0.0 0.0 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.443 0.395 0.076 0.0 0.0 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.39 0.35 0.018 0.0 0.0 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.433 0.396 0.054 0.0 0.0 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.433 0.396 0.054 0.0 0.0 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.431 0.394 0.09 0.0 0.0 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.431 0.394 0.09 0.0 0.0 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.447 0.396 0.054 0.0 0.0 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.447 0.396 0.054 0.0 0.0 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.442 0.395 0.09 0.0 0.0 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.442 0.395 0.09 0.0 0.0 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.389 0.35 0.02 0.0 0.0 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.433 0.396 0.061 0.0 0.0 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.433 0.396 0.061 0.0 0.0 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.43 0.394 0.1 0.0 0.0 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.431 0.394 0.1 0.0 0.0 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.446 0.396 0.061 0.0 0.0 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.446 0.396 0.061 0.0 0.0 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.44 0.395 0.1 0.0 0.0 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.441 0.395 0.1 0.0 0.0 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.388 0.35 0.023 0.0 0.0 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.431 0.396 0.07 0.0 0.0 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.431 0.396 0.07 0.0 0.0 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.429 0.394 0.116 0.0 0.0 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.43 0.394 0.116 0.0 0.0 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.444 0.396 0.07 0.0 0.0 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.444 0.396 0.07 0.0 0.0 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.439 0.394 0.117 0.0 0.0 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.439 0.394 0.117 0.0 0.0 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.386 0.35 0.024 0.0 0.0 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.43 0.395 0.074 0.0 0.0 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.43 0.395 0.074 0.0 0.0 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.428 0.394 0.123 0.0 0.0 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.429 0.394 0.123 0.0 0.0 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.443 0.396 0.074 0.0 0.0 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.442 0.396 0.074 0.0 0.0 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.437 0.394 0.123 0.0 0.0 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.438 0.394 0.123 0.0 0.0 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.384 0.35 0.026 0.0 0.0 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.429 0.395 0.078 0.0 0.0 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.429 0.395 0.078 0.0 0.0 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.427 0.394 0.129 0.0 0.0 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.428 0.394 0.129 0.0 0.0 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.44 0.396 0.078 0.0 0.0 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.44 0.396 0.078 0.0 0.0 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.436 0.394 0.129 0.0 0.0 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.436 0.394 0.129 0.0 0.0 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.379 0.349 0.027 0.0 0.0 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.426 0.395 0.081 0.0 0.0 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.426 0.395 0.081 0.0 0.0 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.425 0.393 0.134 0.0 0.0 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.426 0.393 0.134 0.0 0.0 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.434 0.395 0.081 0.0 0.0 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.434 0.395 0.081 0.0 0.0 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.432 0.394 0.134 0.0 0.0 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.433 0.394 0.134 0.0 0.0 0.0
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.388 0.349 0.01 0.0 0.0 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.432 0.395 0.032 0.0 0.0 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.432 0.395 0.032 0.0 0.0 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.429 0.394 0.053 0.0 0.0 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.431 0.394 0.053 0.0 0.0 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.444 0.396 0.032 0.0 0.0 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.445 0.396 0.032 0.0 0.0 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.442 0.394 0.053 0.0 0.0 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.388 0.35 0.022 0.0 0.0 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.432 0.396 0.066 0.0 0.0 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.432 0.396 0.066 0.0 0.0 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.43 0.394 0.109 0.0 0.0 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.43 0.394 0.109 0.0 0.0 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.445 0.396 0.066 0.0 0.0 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.445 0.396 0.066 0.0 0.0 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.439 0.394 0.109 0.0 0.0 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.44 0.394 0.109 0.0 0.0 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2.37 4.42 9498 0.358 0.0 0.056 0.0 0.0 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.37 0.347 0.238 0.0 0.0 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.418 0.393 0.294 0.0 0.0 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.418 0.393 0.294 0.0 0.0 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.42 0.393 0.349 0.0 0.0 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.42 0.393 0.349 0.0 0.0 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.424 0.393 0.294 0.0 0.0 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.424 0.393 0.294 0.0 0.0 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.425 0.393 0.349 0.0 0.0 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.426 0.393 0.349 0.0 0.0 0.0

Cash Flow

No Data to Show for Cash Flow

Site and Source Summary


Total Energy (kBtu) Energy Per Total Building Area (kBtu/ft^2) Energy Per Conditioned Building Area (kBtu/ft^2)
Total Site Energy 4653478.9 55.2 55.2
Net Site Energy 4653478.9 55.2 55.2
Total Source Energy 14737551.9 174.7 174.7
Net Source Energy 14737551.9 174.7 174.7

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613

Schedule Overview


Schedule Type Limits Rules Use Count
Air Velocity Schedule Velocity 0 3
Always On Dimensionless 0 90
CHW Temp Temperature 3 1
Clothing Schedule ClothingInsulation 1 3
CW Temp Temperature 3 1
Make-up air unit Occ Sch Dimensionless 7 2
Makeup-Air Unit Supply Air Temp Temperature 0 1
NECB-A-Electric-Equipment Dimensionless 3 1
NECB-A-Lighting Dimensionless 3 1
NECB-A-Occupancy Dimensionless 3 1
NECB-A-Service Water Heating Dimensionless 3 1
NECB-A-Thermostat Setpoint-Cooling Temperature 3 3
NECB-A-Thermostat Setpoint-Heating Temperature 3 3
NECB-Activity ActivityLevel 0 90
NECB-G-Electric-Equipment Dimensionless 3 89
NECB-G-Lighting Dimensionless 3 89
NECB-G-Occupancy Dimensionless 3 89
NECB-G-Service Water Heating Dimensionless 3 79
NECB-G-Thermostat Setpoint-Cooling Temperature 3 180
NECB-G-Thermostat Setpoint-Heating Temperature 3 180
ON_OFF_ALWAYS_OFF Availability 3 89
Schedule Ruleset 10 0 1
Schedule Ruleset 100 0 1
Schedule Ruleset 101 0 1
Schedule Ruleset 102 0 1
Schedule Ruleset 103 0 1
Schedule Ruleset 104 0 1
Schedule Ruleset 105 0 1
Schedule Ruleset 106 0 1
Schedule Ruleset 107 0 1
Schedule Ruleset 108 0 1
Schedule Ruleset 109 0 1
Schedule Ruleset 11 0 1
Schedule Ruleset 110 0 1
Schedule Ruleset 111 0 1
Schedule Ruleset 112 0 1
Schedule Ruleset 113 0 1
Schedule Ruleset 114 0 1
Schedule Ruleset 115 0 1
Schedule Ruleset 116 0 1
Schedule Ruleset 117 0 1
Schedule Ruleset 118 0 1
Schedule Ruleset 119 0 1
Schedule Ruleset 12 0 1
Schedule Ruleset 120 0 1
Schedule Ruleset 121 0 1
Schedule Ruleset 122 0 1
Schedule Ruleset 123 0 1
Schedule Ruleset 124 0 1
Schedule Ruleset 125 0 1
Schedule Ruleset 126 0 1
Schedule Ruleset 127 0 1
Schedule Ruleset 128 0 1
Schedule Ruleset 129 0 1
Schedule Ruleset 13 0 1
Schedule Ruleset 130 0 1
Schedule Ruleset 131 0 1
Schedule Ruleset 132 0 1
Schedule Ruleset 133 0 1
Schedule Ruleset 134 0 1
Schedule Ruleset 135 0 1
Schedule Ruleset 136 0 1
Schedule Ruleset 137 0 1
Schedule Ruleset 138 0 1
Schedule Ruleset 139 0 1
Schedule Ruleset 14 0 1
Schedule Ruleset 140 0 1
Schedule Ruleset 141 0 1
Schedule Ruleset 142 0 1
Schedule Ruleset 143 0 1
Schedule Ruleset 144 0 1
Schedule Ruleset 145 0 1
Schedule Ruleset 146 0 1
Schedule Ruleset 147 0 1
Schedule Ruleset 148 0 1
Schedule Ruleset 149 0 1
Schedule Ruleset 15 0 1
Schedule Ruleset 150 0 1
Schedule Ruleset 151 0 1
Schedule Ruleset 152 0 1
Schedule Ruleset 153 0 1
Schedule Ruleset 154 0 1
Schedule Ruleset 155 0 1
Schedule Ruleset 156 0 1
Schedule Ruleset 157 0 1
Schedule Ruleset 158 0 1
Schedule Ruleset 159 0 1
Schedule Ruleset 16 0 1
Schedule Ruleset 160 0 1
Schedule Ruleset 161 0 1
Schedule Ruleset 162 0 1
Schedule Ruleset 163 0 1
Schedule Ruleset 164 0 1
Schedule Ruleset 165 0 1
Schedule Ruleset 166 0 1
Schedule Ruleset 167 0 1
Schedule Ruleset 168 0 1
Schedule Ruleset 169 0 1
Schedule Ruleset 17 0 1
Schedule Ruleset 170 0 1
Schedule Ruleset 171 0 1
Schedule Ruleset 172 0 1
Schedule Ruleset 173 0 1
Schedule Ruleset 174 0 1
Schedule Ruleset 175 0 1
Schedule Ruleset 176 0 1
Schedule Ruleset 177 0 1
Schedule Ruleset 178 0 1
Schedule Ruleset 179 0 1
Schedule Ruleset 18 0 1
Schedule Ruleset 180 0 1
Schedule Ruleset 181 0 1
Schedule Ruleset 182 0 1
Schedule Ruleset 183 0 1
Schedule Ruleset 184 0 1
Schedule Ruleset 185 0 1
Schedule Ruleset 186 0 1
Schedule Ruleset 187 0 1
Schedule Ruleset 188 0 1
Schedule Ruleset 189 0 1
Schedule Ruleset 19 0 1
Schedule Ruleset 190 0 1
Schedule Ruleset 191 0 1
Schedule Ruleset 192 0 1
Schedule Ruleset 193 0 1
Schedule Ruleset 194 0 1
Schedule Ruleset 195 0 1
Schedule Ruleset 196 0 1
Schedule Ruleset 197 0 1
Schedule Ruleset 198 0 1
Schedule Ruleset 199 0 1
Schedule Ruleset 20 0 1
Schedule Ruleset 200 0 1
Schedule Ruleset 201 0 1
Schedule Ruleset 202 0 1
Schedule Ruleset 203 0 1
Schedule Ruleset 204 0 1
Schedule Ruleset 205 0 1
Schedule Ruleset 206 0 1
Schedule Ruleset 207 0 1
Schedule Ruleset 208 0 1
Schedule Ruleset 209 0 1
Schedule Ruleset 21 0 1
Schedule Ruleset 210 0 1
Schedule Ruleset 211 0 1
Schedule Ruleset 212 0 1
Schedule Ruleset 213 0 1
Schedule Ruleset 214 0 1
Schedule Ruleset 215 0 1
Schedule Ruleset 216 0 1
Schedule Ruleset 217 0 1
Schedule Ruleset 218 0 1
Schedule Ruleset 219 0 1
Schedule Ruleset 22 0 1
Schedule Ruleset 220 0 1
Schedule Ruleset 221 0 1
Schedule Ruleset 222 0 1
Schedule Ruleset 223 0 1
Schedule Ruleset 224 0 1
Schedule Ruleset 225 0 1
Schedule Ruleset 226 0 1
Schedule Ruleset 227 0 1
Schedule Ruleset 228 0 1
Schedule Ruleset 229 0 1
Schedule Ruleset 23 0 1
Schedule Ruleset 230 0 1
Schedule Ruleset 231 0 1
Schedule Ruleset 232 0 1
Schedule Ruleset 233 0 1
Schedule Ruleset 234 0 1
Schedule Ruleset 235 0 1
Schedule Ruleset 236 0 1
Schedule Ruleset 237 0 1
Schedule Ruleset 238 0 1
Schedule Ruleset 239 0 1
Schedule Ruleset 24 0 1
Schedule Ruleset 240 0 1
Schedule Ruleset 241 0 1
Schedule Ruleset 242 0 1
Schedule Ruleset 25 0 1
Schedule Ruleset 26 0 1
Schedule Ruleset 27 0 1
Schedule Ruleset 28 0 1
Schedule Ruleset 29 0 1
Schedule Ruleset 3 0 1
Schedule Ruleset 30 0 1
Schedule Ruleset 31 0 1
Schedule Ruleset 32 0 1
Schedule Ruleset 33 0 1
Schedule Ruleset 34 0 1
Schedule Ruleset 35 0 1
Schedule Ruleset 36 0 1
Schedule Ruleset 37 0 1
Schedule Ruleset 38 0 1
Schedule Ruleset 39 0 1
Schedule Ruleset 4 0 1
Schedule Ruleset 40 0 1
Schedule Ruleset 41 0 1
Schedule Ruleset 42 0 1
Schedule Ruleset 43 0 1
Schedule Ruleset 44 0 1
Schedule Ruleset 45 0 1
Schedule Ruleset 46 0 1
Schedule Ruleset 47 0 1
Schedule Ruleset 48 0 1
Schedule Ruleset 49 0 1
Schedule Ruleset 5 0 1
Schedule Ruleset 50 0 1
Schedule Ruleset 51 0 1
Schedule Ruleset 52 0 1
Schedule Ruleset 53 0 1
Schedule Ruleset 54 0 1
Schedule Ruleset 55 0 1
Schedule Ruleset 56 0 1
Schedule Ruleset 57 0 1
Schedule Ruleset 58 0 1
Schedule Ruleset 59 0 1
Schedule Ruleset 6 0 1
Schedule Ruleset 60 0 1
Schedule Ruleset 61 0 1
Schedule Ruleset 62 0 1
Schedule Ruleset 63 0 1
Schedule Ruleset 64 0 1
Schedule Ruleset 65 0 1
Schedule Ruleset 66 0 1
Schedule Ruleset 67 0 1
Schedule Ruleset 68 0 1
Schedule Ruleset 69 0 1
Schedule Ruleset 7 0 1
Schedule Ruleset 70 0 1
Schedule Ruleset 71 0 1
Schedule Ruleset 72 0 1
Schedule Ruleset 73 0 1
Schedule Ruleset 74 0 1
Schedule Ruleset 75 0 1
Schedule Ruleset 76 0 1
Schedule Ruleset 77 0 1
Schedule Ruleset 78 0 1
Schedule Ruleset 79 0 1
Schedule Ruleset 8 0 1
Schedule Ruleset 80 0 1
Schedule Ruleset 81 0 1
Schedule Ruleset 82 0 1
Schedule Ruleset 83 0 1
Schedule Ruleset 84 0 1
Schedule Ruleset 85 0 1
Schedule Ruleset 86 0 1
Schedule Ruleset 87 0 1
Schedule Ruleset 88 0 1
Schedule Ruleset 89 0 1
Schedule Ruleset 9 0 1
Schedule Ruleset 90 0 1
Schedule Ruleset 91 0 1
Schedule Ruleset 92 0 1
Schedule Ruleset 93 0 1
Schedule Ruleset 94 0 1
Schedule Ruleset 95 0 1
Schedule Ruleset 96 0 1
Schedule Ruleset 97 0 1
Schedule Ruleset 98 0 1
Schedule Ruleset 99 0 1
Service Water Loop Temp - 140F Temperature 0 2
Supply Air Temp Temperature 0 1
VAV with Reheat Occ Sch Dimensionless 7 2
Water Heater Ambient Temp Schedule - 70F Temperature 0 1
Work Efficiency Schedule Dimensionless 0 3